Voltage-controlled smart decoupling device VCSD
- VCSD: Voltage Controlled Smart Decoupling Device
- Protection in case of transient, temporary and long-duration overvoltages
- Does not negatively affect cathodic protection equipment
- Adjustable response threshold for flexible use in a wide range of applications and operating states
EB 9V LI Block Battery
Since Part No. 923 099 is a dangerous good, dispatch is only possible in Germany.
Part No. 923099
EB 9V LI1300 80
item
GTIN: 4013364274686, customs tariff number: 85065090, gross weight: 0.046 KG, packaging unit: 1 ST
VCSD 40 IP65
Voltage-controlled smart decoupling device for use in widely distributed and highly networked electrical systems which are influenced by external voltages from various sources (e.g. high-voltage systems, traction power supply systems, low-voltage systems, lightning interference).
- High discharge capacity in case of transient, temporary and long-duration external voltages
- Ensures a save operation of the pipeline system due to low limiting voltages
- Easy integration into monitoring and control systems due to digital and analog in- and outputs
- High discharge capacity in case of transient, temporary and long-duration external voltages
- Ensures a save operation of the pipeline system due to low limiting voltages
- Easy integration into monitoring and control systems due to digital and analog in- and outputs
Part No. 923401
VCSD 40 IP65
item
GTIN: 4013364237766, customs tariff number: 85363030, gross weight: 13.76 KG, packaging unit: 1 ST
Voltage-controlled decoupling device VCSD
Voltage-controlled decoupling device
For protection in case of transient, temporary and long-duration overvoltages
Discharge current transient: (10/350 s): 100 kA
Temporary discharge current (16.7 Hz, 50 Hz, 60 Hz):
850 Arms (up to 200 ms)
Long-duration discharge current (16.7 Hz, 50 Hz, 60 Hz):
45 A (permanent)
Transient limiting voltage (up to 1 ms): 1.25 kV
Transient limiting voltage (ACrms) (1 to 20 ms):
940 V (1 kV as per German AfK recommendation no. 3)
Temporary limiting voltage (ACrms) (20 to 100 ms):
660 V (1 kV as per German AfK recommendation no. 3)
Temporary limiting voltage (ACrms) (100 to 200 ms):
400 V (1 kV as per German AfK recommendation no. 3)
Long-duration limiting voltage (ACrms) (> 200 ms):
max. 60 V (adjustable 3 to 50 V)
(protection of people as per German AfK recommendation 3/GW22)
With digital and analogue inputs/outputs
for remote monitoring and control
Brand: DEHN
Type: VCSD 40 IP65
Part No.: 923401
or equivalent.
Voltage-controlled decoupling device
For protection in case of transient, temporary and long-duration overvoltages
Discharge current transient: (10/350 s): 100 kA
Temporary discharge current (16.7 Hz, 50 Hz, 60 Hz):
850 Arms (up to 200 ms)
Long-duration discharge current (16.7 Hz, 50 Hz, 60 Hz):
45 A (permanent)
Transient limiting voltage (up to 1 ms): 1.25 kV
Transient limiting voltage (ACrms) (1 to 20 ms):
940 V (1 kV as per German AfK recommendation no. 3)
Temporary limiting voltage (ACrms) (20 to 100 ms):
660 V (1 kV as per German AfK recommendation no. 3)
Temporary limiting voltage (ACrms) (100 to 200 ms):
400 V (1 kV as per German AfK recommendation no. 3)
Long-duration limiting voltage (ACrms) (> 200 ms):
max. 60 V (adjustable 3 to 50 V)
(protection of people as per German AfK recommendation 3/GW22)
With digital and analogue inputs/outputs
for remote monitoring and control
Brand: DEHN
Type: VCSD 40 IP65
Part No.: 923401