weiterführende Informationen
DEHNrecord SD
- Multifunctional measuring equipment based on edge computing
- 230 V AC supply voltage, alternatively 24 V DC external
- Compact dimensions (5 modules) for simple integration and retrofitting
- Installation benefits thanks to adaption to SPDs via busbar
- Voltage quality measurement according to EN 61000-4-30, class-A-certified
- Limit values according to EN 50160
- Option of additional definition of individual PQ limit values
- Measurement of temporary / power-frequency overvoltages according to EN50550
- Measurement of load profile and power
- Integrated digital inputs and outputs, logically linkable
- Communication link through Modbus TCP and MQTT 3.1 Azure
DRC SD 1 1
Multifunctional measurement and analysis device for monitoring voltage quality
Part No. 910920
DRC SD 1 1
item
GTIN: 4013364460263, customs tariff number: 90303200, gross weight: 0.51 KG, packaging unit: 1 ST
Integral, multifunctional measuring equipment
based on edge computing with the following functions:
Supply voltage 230 V, 1-phase via L1, e.g.
via busbar directly from surge arrester /
no additional wiring or backup fuse required
Compact housing for simple integration
and retrofitting, 5 modules in width / DIN rail mounting
Voltage quality measurement according to EN 61000-4-30,
Class-A-certified
Permanent transmission of the standardised mean values
Fault record transmitted in the event of limit value violation /
Resulting in significantly reduced data volume
for easier handling
Limit values as per EN 50160 / option of
additional definition of individual PQ limit values
Triggerable transmission of the fault record also
without limit value violation / customised triggering
via device button or Web-based
PQ characteristics as per
marking concept according to EN 61000-4-30
Four-pole load current and power measurement by means of
external current coils for measurements of up to either
100 A (split-core current transformer) or up to
1,000 A (Rogowski coils) (cable lengths 3 m)
Measured value transmission of 5-minute mean values
Measurement with the correct polarity for detection
of reference and regenerative power
Measurement of temporary / power-frequency
overvoltages according to EN50550, including customised
parameterisation options; e.g. for reporting
low voltage
Event messages possible via cloud monitor,
digital outputs and via
email notifications
Integrated parameterizable I/O interfaces
3x inputs, 2x outputs, for event-focussed control commands
Integrated measurement point concept
Adaptable by means of busbars directly
to surge protective devices
Communication link via Modbus
TCP/IP interface and MQTT protocol (3.1, Azure-based)
Measured value display either via
DEHN Cloudmonitor or via external
company-specific cloud platforms / Alternatively
by reading from the Modbus register
GPS location positioning for possible
creation of PQ maps
Web-based device configuration and firmware updates
Brand: DEHN
Type: DRC SD 1 1
Part No.: 910920
or equivalent.
based on edge computing with the following functions:
Supply voltage 230 V, 1-phase via L1, e.g.
via busbar directly from surge arrester /
no additional wiring or backup fuse required
Compact housing for simple integration
and retrofitting, 5 modules in width / DIN rail mounting
Voltage quality measurement according to EN 61000-4-30,
Class-A-certified
Permanent transmission of the standardised mean values
Fault record transmitted in the event of limit value violation /
Resulting in significantly reduced data volume
for easier handling
Limit values as per EN 50160 / option of
additional definition of individual PQ limit values
Triggerable transmission of the fault record also
without limit value violation / customised triggering
via device button or Web-based
PQ characteristics as per
marking concept according to EN 61000-4-30
Four-pole load current and power measurement by means of
external current coils for measurements of up to either
100 A (split-core current transformer) or up to
1,000 A (Rogowski coils) (cable lengths 3 m)
Measured value transmission of 5-minute mean values
Measurement with the correct polarity for detection
of reference and regenerative power
Measurement of temporary / power-frequency
overvoltages according to EN50550, including customised
parameterisation options; e.g. for reporting
low voltage
Event messages possible via cloud monitor,
digital outputs and via
email notifications
Integrated parameterizable I/O interfaces
3x inputs, 2x outputs, for event-focussed control commands
Integrated measurement point concept
Adaptable by means of busbars directly
to surge protective devices
Communication link via Modbus
TCP/IP interface and MQTT protocol (3.1, Azure-based)
Measured value display either via
DEHN Cloudmonitor or via external
company-specific cloud platforms / Alternatively
by reading from the Modbus register
GPS location positioning for possible
creation of PQ maps
Web-based device configuration and firmware updates
Brand: DEHN
Type: DRC SD 1 1
Part No.: 910920
or equivalent.
DRC SD 2 1
Multifunctional measurement and analysis device for monitoring voltage quality
Part No. 910921
DRC SD 2 1
item
GTIN: 4013364460270, customs tariff number: 90303200, gross weight: 0.51 KG, packaging unit: 1 ST
Integral, multifunctional measuring equipment
based on edge computing with the following functions:
Power supply 24 V DC
Compact housing for simple integration
and retrofitting, 5 modules in width / DIN rail mounting
Voltage quality measurement according to EN 61000-4-30,
Class-A-certified
Permanent transmission of the standardised mean values
Fault record transmitted in the event of limit value violation /
Resulting in significantly reduced data volume
for easier handling
Limit values as per EN 50160 / option of
additional definition of individual PQ limit values
Triggerable transmission of the fault current also
without limit value violation / customised triggering
via device button or Web-based
PQ characteristics as per
marking concept according to EN 61000-4-30
Four-pole load current and power measurement by means of
external current coils for measurements of up to either
100 A (split-core current transformer) or up to
1,000 A (Rogowski coils) (cable lengths 3 m)
Measured value transmission of 5-minute mean values
Measurement with the correct polarity for detection
of reference and regenerative power
Measurement of temporary / power-frequency
overvoltages according to EN50550, including customised
parameterisation options; e.g. for reporting
low voltage
Event messages possible via cloud monitor,
digital outputs and via
email notifications
Integrated parameterizable I/O interfaces
3x inputs, 2x outputs, for event-focussed control commands
Integrated measurement point concept
Adaptable by means of busbars directly
to surge protective devices
Communication link via Modbus
TCP/IP interface and MQTT protocol (3.1, Azure-based)
Measured value display either via
DEHN Cloudmonitor or via external
company-specific cloud platforms / Alternatively
by reading from the Modbus register
GPS location positioning for possible
creation of PQ maps
Web-based device configuration and firmware updates
Brand: DEHN
Type: DRC SD 2 1
Part No.: 910921
or equivalent.
based on edge computing with the following functions:
Power supply 24 V DC
Compact housing for simple integration
and retrofitting, 5 modules in width / DIN rail mounting
Voltage quality measurement according to EN 61000-4-30,
Class-A-certified
Permanent transmission of the standardised mean values
Fault record transmitted in the event of limit value violation /
Resulting in significantly reduced data volume
for easier handling
Limit values as per EN 50160 / option of
additional definition of individual PQ limit values
Triggerable transmission of the fault current also
without limit value violation / customised triggering
via device button or Web-based
PQ characteristics as per
marking concept according to EN 61000-4-30
Four-pole load current and power measurement by means of
external current coils for measurements of up to either
100 A (split-core current transformer) or up to
1,000 A (Rogowski coils) (cable lengths 3 m)
Measured value transmission of 5-minute mean values
Measurement with the correct polarity for detection
of reference and regenerative power
Measurement of temporary / power-frequency
overvoltages according to EN50550, including customised
parameterisation options; e.g. for reporting
low voltage
Event messages possible via cloud monitor,
digital outputs and via
email notifications
Integrated parameterizable I/O interfaces
3x inputs, 2x outputs, for event-focussed control commands
Integrated measurement point concept
Adaptable by means of busbars directly
to surge protective devices
Communication link via Modbus
TCP/IP interface and MQTT protocol (3.1, Azure-based)
Measured value display either via
DEHN Cloudmonitor or via external
company-specific cloud platforms / Alternatively
by reading from the Modbus register
GPS location positioning for possible
creation of PQ maps
Web-based device configuration and firmware updates
Brand: DEHN
Type: DRC SD 2 1
Part No.: 910921
or equivalent.
DRC SD ICS 100
With the DEHNrecord SD ICS, impulse currents of up to 100 kA can be detected on insulated cables (8/20 µs; 10/350 µs).
Part No. 910935
DRC SD ICS 100
item
GTIN: 4013364460676, customs tariff number: 90303370, gross weight: 0.172 KG, packaging unit: 1 ST
Impulse current sensor with connecting cable
For measuring impulse currents of up to 100 kA
Max. recording duration 5 sec.
Amplitude resolution 100 A
Sampling rate 1 µs
Configurable trigger threshold via Web server
of the DRC SD 1 1 or DRC SD 2 1
Connecting cable length 3 m
Brand: DEHN
Type: DRC SD ICS 100
Part No.: 910935
or equivalent.
For measuring impulse currents of up to 100 kA
Max. recording duration 5 sec.
Amplitude resolution 100 A
Sampling rate 1 µs
Configurable trigger threshold via Web server
of the DRC SD 1 1 or DRC SD 2 1
Connecting cable length 3 m
Brand: DEHN
Type: DRC SD ICS 100
Part No.: 910935
or equivalent.
DRC SD SCS 100
Split-core current transformer for electronic measurement of alternating current (AC) with galvanic isolation between the primary circuit (power) and secondary circuit (measurement) up to 300 V CAT III.
Part No. 910936
DRC SD SCS 100
item
GTIN: 4013364460683, customs tariff number: 90303370, gross weight: 0.149 KG, packaging unit: 1 ST
Split-core current transformer for electronic
measurement of alternating current (AC) with galvanic
isolation between the primary (power) and secondary
circuit (measurement) up to 300 V CAT III.
Accuracy class 1 (IEC 61869-2)
Nominal primary current 100 A
Expanded primary current 120 A
Thermal rated short-time current max. 6 kA @ 50 Hz
Dynamic nominal current max. 3 kA @ 50 Hz
Nominal frequency 50 Hz
Frequency bandwidth (-3 dB) min. 1.5 kHz
Connecting cable length 1 m
Max. cable diameter 16 mm
Brand: DEHN
Type: DRC SD SCS 100
Part No.: 910936
or equivalent.
measurement of alternating current (AC) with galvanic
isolation between the primary (power) and secondary
circuit (measurement) up to 300 V CAT III.
Accuracy class 1 (IEC 61869-2)
Nominal primary current 100 A
Expanded primary current 120 A
Thermal rated short-time current max. 6 kA @ 50 Hz
Dynamic nominal current max. 3 kA @ 50 Hz
Nominal frequency 50 Hz
Frequency bandwidth (-3 dB) min. 1.5 kHz
Connecting cable length 1 m
Max. cable diameter 16 mm
Brand: DEHN
Type: DRC SD SCS 100
Part No.: 910936
or equivalent.
DRC SD RCS 1000
Rogowski coil current transformer for electronic measurement of alternating current (AC) with galvanic isolation between the primary circuit (power) and secondary circuit (measurement) up to 1,000 V CAT III.
Part No. 910937
DRC SD RCS 1000 3M
item
GTIN: 4013364460690, customs tariff number: 90303370, gross weight: 0.21 KG, packaging unit: 1 ST
Rogowski coil current transformer
for electronic measurement
of alternating current (AC) with galvanic
isolation between the primary (power)
and secondary circuit (measurement) up to 1,000 V CAT III
Accuracy class 1 (IEC 61869-2)
Nominal primary current 1,000 A
Expanded primary current 2,000 A
Nominal frequency 50 Hz
Frequency bandwidth (-3 dB) 3 kHz
Connecting cable length 3 m
Max. cable diameter 95 mm
Brand: DEHN
Type: DRC SD RCS 1000 3M
Part No.: 910937
or equivalent.
for electronic measurement
of alternating current (AC) with galvanic
isolation between the primary (power)
and secondary circuit (measurement) up to 1,000 V CAT III
Accuracy class 1 (IEC 61869-2)
Nominal primary current 1,000 A
Expanded primary current 2,000 A
Nominal frequency 50 Hz
Frequency bandwidth (-3 dB) 3 kHz
Connecting cable length 3 m
Max. cable diameter 95 mm
Brand: DEHN
Type: DRC SD RCS 1000 3M
Part No.: 910937
or equivalent.
DRC SD RCS 1000
Rogowski coil current transformer for electronic measurement of alternating current (AC) with galvanic isolation between the primary circuit (power) and secondary circuit (measurement) up to 1,000 V CAT III.
Part No. 910938
DRC SD RCS 1000 1M
item
GTIN: 4013364467668, customs tariff number: 90303370, gross weight: 0.147 KG, packaging unit: 1 ST
Rogowski coil current transformer
for electronic measurement
of alternating current (AC) with galvanic
isolation between the primary (power)
and secondary circuit (measurement) up to 1,000 V CAT III
Accuracy class 1 (IEC 61869-2)
Nominal primary current 1,000 A
Expanded primary current 2,000 A
Nominal frequency 50 Hz
Frequency bandwidth (-3 dB) 3 kHz
Connecting cable length 1 m
Max. cable diameter 95 mm
Brand: DEHN
Type: DRC SD RCS 1000 1M
Part No.: 910938
or equivalent.
for electronic measurement
of alternating current (AC) with galvanic
isolation between the primary (power)
and secondary circuit (measurement) up to 1,000 V CAT III
Accuracy class 1 (IEC 61869-2)
Nominal primary current 1,000 A
Expanded primary current 2,000 A
Nominal frequency 50 Hz
Frequency bandwidth (-3 dB) 3 kHz
Connecting cable length 1 m
Max. cable diameter 95 mm
Brand: DEHN
Type: DRC SD RCS 1000 1M
Part No.: 910938
or equivalent.