DEHNpipe
- Parallel or series connection
- Made of corrosion-resistant stainless steel
- Arrester for protecting a second interface (data or power side) available
Types for Ex (i) and Ex (d) applications
- For protecting intrinsically safe measuring circuits and bus systems Ex (i)
- Type in a flameproof enclosure Ex (d)
Variety of approvals
- Approvals depending on the arrester: IECEx, ATEX, FISCO, CSA Hazloc
DPI MD
DPI MD EX
DPI MD EX
DPI CD EXI
GTIN: 4013364101784, customs tariff number: 85363010, gross weight: 0.183 KG, packaging unit: 1 ST
Surge arrester DEHNpipe, SPD class TYPE 2/1,
tested acc. to EN 61643-21 and energy coordinated
acc. to IEC 61643-22, in V2A, IP67, Ex(i)-version,
for screwing into 2-conductor process field devices,
parallel protection of a floating pair as well as
intrinsically safe bus systems
Max. continuous operating voltage DC (UC): 32 V
Max. continuous operating a.c. voltage (UC): 22,6 V
Nominal current (IL): 0,55 A
C2 Total nominal discharge current (8/20 µs) (In): 10 kA
C2 Nominal discharge current (8/20 µs) line-line (In): 150 A
D1 Lightning impulse current (10/350 µs) line-PG (Iimp): 1 kA
Cut-off frequency line-line (fG): 67 MHz
Degree of protection: Aufbau in IP 67
For mounting on (field / device side): M20 x 1,5 Außengewinde
Brand: DEHN
Type: DPI CD EXI 24 M
Part No.: 929961
or equivalent.
DPI CD EXI
GTIN: 4013364101807, customs tariff number: 85363010, gross weight: 0.196 KG, packaging unit: 1 ST
Surge arrester DEHNpipe, SPD class TYPE 2/1,
tested acc. to EN 61643-21 and energy coordinated
acc. to IEC 61643-22, in V2A, IP67, Ex(i)-version,
for screwing into 2-conductor process field devices,
parallel protection of a floating pair as well as
intrinsically safe bus systems
Max. continuous operating voltage DC (UC): 32 V
Max. continuous operating a.c. voltage (UC): 22,6 V
Nominal current (IL): 0,55 A
C2 Total nominal discharge current (8/20 µs) (In): 10 kA
C2 Nominal discharge current (8/20 µs) line-line (In): 150 A
D1 Lightning impulse current (10/350 µs) line-PG (Iimp): 1 kA
Cut-off frequency line-line (fG): 67 MHz
Degree of protection: Aufbau in IP 67
For mounting on (field / device side): 1/2-14 NPT Außengewinde
Brand: DEHN
Type: DPI CD EXI 24 N
Part No.: 929963
or equivalent.
DPI CD EXD
GTIN: 4013364101791, customs tariff number: 85363010, gross weight: 0.183 KG, packaging unit: 1 ST
Surge arrester DEHNpipe, SPD class TYPE 2/1,
tested acc. to EN 61643-21, in V4A, IP67,
Ex(d)-version, for screwing into 2-conductor
process field devices, parallel protection of a
floating pair as well as bus systems in
Ex zone 1 or 2
Max. continuous operating voltage DC (UC): 32 V
Max. continuous operating a.c. voltage (UC): 22,6 V
Nominal current (IL): 0,55 A
C2 Total nominal discharge current (8/20 µs) (In): 10 kA
D1 Lightning impulse current (10/350 µs) line-PG (Iimp): 1 kA
Cut-off frequency line-line (fG): 67 MHz
Degree of protection: Aufbau in IP 67
For mounting on (field / device side): M20 x 1,5 Außengewinde
Brand: DEHN
Type: DPI CD EXD 24 M
Part No.: 929962
or equivalent.
DPI CD EXD
GTIN: 4013364101814, customs tariff number: 85363010, gross weight: 0.183 KG, packaging unit: 1 ST
Surge arrester DEHNpipe, SPD class TYPE 2/1,
tested acc. to EN 61643-21, in V4A, IP67,
Ex(d)-version, for screwing into 2-conductor
process field devices, parallel protection of a
floating pair as well as bus systems in
Ex zone 1 or 2
Max. continuous operating voltage DC (UC): 32 V
Max. continuous operating a.c. voltage (UC): 22,6 V
Nominal current (IL): 0,55 A
C2 Total nominal discharge current (8/20 µs) (In): 10 kA
D1 Lightning impulse current (10/350 µs) line-PG (Iimp): 1 kA
Cut-off frequency line-line (fG): 67 MHz
Degree of protection: Aufbau in IP 67
For mounting on (field / device side): 1/2-14 NPT Außengewinde
Brand: DEHN
Type: DPI CD EXD 24 N
Part No.: 929964
or equivalent.
DPI CD HF EXD
GTIN: 4013364120761, customs tariff number: 85363010, gross weight: 0.286 KG, packaging unit: 1 ST
DEHNpipe surge arrester of SPD class Type 2 / P1,
tested in accordance with EN 61643-21, V4A, IP 67,
available as Ex (d) type, to be screwed onto 2-
conductor field devices, serial protection of an
unearthed pair and bus systems in explosion
protection zone 1 or 2.
Max. continuous operating voltage DC (UC): 6 V
Max. continuous operating a.c. voltage (UC): 4,2 V
Nominal current at 80°C (IL): 0,1 A
C2 Total nominal discharge current (8/20 µs) (In): 20 kA
Cut-off frequency line-line (fG): 100 MHz
Degree of protection: Aufbau in IP 67
For mounting on (field / device side): M20 x 1,5 Außengewinde
Brand: DEHN
Type: DPI CD HF EXD 5 M
Part No.: 929971
or equivalent.
DPI CD EXD 230 24
Additional safety due to fault-proof Y circuit for 120 / 230 V power supply systems.
II 2 G Ex d IIC T5/T6 version universally applicable in hazardous zones 1 and 2. Certified to CSA and USA Hazloc standards.
DPI CD EXD 230 24
Additional safety due to fault-proof Y circuit for 120 / 230 V power supply systems.
II 2 G Ex d IIC T5/T6 version universally applicable in hazardous zones 1 and 2. Certified to CSA and USA Hazloc standards.
DPI CD EXI+D 2X24
GTIN: 4013364137387, customs tariff number: 85363010, gross weight: 0.247 KG, packaging unit: 1 ST
surge arresters
of SPD class Type 2 / P1
DEHNpipe, tested to
EN 61643-21, in V2A, IP67,
in Ex (i) + (d) version,
for the protection of two
unearthed signal circuits
or the supply circuit
of the field device and a
signal circuit in Ex zone 1 or 2.
Max. continuous operating voltage DC (UC): 36 V
Max. continuous operating a.c. voltage (UC): 25,4 V
Nominal current (IL): 0,55 A
C2 Total nominal discharge current (8/20 µs) (In): 20 kA
D1 Lightning impulse current (10/350 µs) line-PG (Iimp): 1,5 kA
Degree of protection: Aufbau in IP 67
For mounting on (field / device side): M20 x 1,5 Außengewinde
Brand: DEHN
Type: DPI CD EXI+D 2X24 M
Part No.: 929950
or equivalent.
DPI CD EXI+D 2X24
GTIN: 4013364137394, customs tariff number: 85363010, gross weight: 0.247 KG, packaging unit: 1 ST
surge arresters
of SPD class Type 2 / P1
DEHNpipe, tested to
EN 61643-21, in V2A, IP67,
in Ex (i) + (d) version,
for screwing into field devices
for the protection of two
unearthed signal circuits
or the supply circuit
of the field device and a
signal circuit in Ex zone 1 or 2.
Max. continuous operating voltage DC (UC): 36 V
Max. continuous operating a.c. voltage (UC): 25,4 V
Nominal current (IL): 0,55 A
C2 Total nominal discharge current (8/20 µs) (In): 20 kA
D1 Lightning impulse current (10/350 µs) line-PG (Iimp): 1,5 kA
Degree of protection: Aufbau in IP 67
For mounting on (field / device side): 1/2-14 NPT Außengewinde
Brand: DEHN
Type: DPI CD EXI+D 2X24 N
Part No.: 929951
or equivalent.
DPI CD EXI+D EAS 15 M
Surge arrester in an intrinsically safe flameproof enclosure for use in potentially explosive atmospheres for protecting field devices with Ethernet network termination interface, PROFIBUS PA and measuring and control circuits. Fulfils the requirements of 2-WISE and FISCO Insulation strength >500 V line-earth.
GTIN: 4013364534544, customs tariff number: 85363010, gross weight: 0.187 KG, packaging unit: 1 ST
DEHNpipe CD EXI+D EAS 15 M
Surge arrester for the protection of
intrinsically safe measuring and control circuits, spur ports
of Ethernet network termination field devices and PROFIBUS PA
Tested to EN/IEC 61643-21 and
energy-coordinated according to IEC61643-22
in Ex (i) + Ex (d) version,
Signal circuit in zone 1 or 2
fulfils the requirements of 2-WISE and FISCO
SPD class: Type 2 / P3
Impulse category: C1, C2, C3, D1
Max. continuous operating voltage: 30.0 V DC / 21.2 V AC
Nominal current: 0.5 A
C2 nominal discharge current (8/20 µs) per line: 10 kA
C2 Total nominal impulse discharge current (8/20 µs): 20 kA
D1 lightning impulse current (10/350 µs) per line: 1.5 kA
D1 total lightning impulse current (10/350 µs): 3 kA
Male thread M20, on one end
Enclosure in V4A, IP67
Max. continuous operating voltage DC (UC): 32 V
Max. continuous operating a.c. voltage (UC): 22.6 V
Nominal current (IN): 0.55 A
C2 Total nominal discharge current (8/20 µs) (In): 10 kA
C2 Nominal discharge current (8/20 µs) line-line (In): 150 A
D1 Lightning impulse current (10/350 µs) line-PG (Iimp): 1 kA
Cut-off frequency line-line (fG): 67 MHz
Degree of protection: IP 67
For mounting on (field / device side): M20 x 1.5 male thread
Brand: DEHN
Type: DPI CD EXI+D EAS 15 M
Part No.: 929974
or equivalent.
DPI CD EXI+D EAS 15 N
Surge arrester in an intrinsically safe flameproof enclosure for use in potentially explosive atmospheres for protecting field devices with Ethernet network termination interface, PROFIBUS PA and measuring and control circuits. Fulfils the requirements of 2-WISE and FISCO Insulation strength >500 V line-earth.
GTIN: 4013364534551, customs tariff number: 85363010, gross weight: 0.189 KG, packaging unit: 1 ST
DEHNpipe CD EXI+D EAS 15 N
Surge arrester for the protection of
intrinsically safe measuring and control circuits, spur ports of
Ethernet network termination field devices and PROFIBUS PA
Tested to EN/IEC 61643-21 and energetically
coordinated according to IEC61643-22
in Ex (i) + Ex (d) version,
Signal circuit in zone 1 or 2
fulfils the requirements of 2-WISE and FISCO
SPD class: Type 2 / P3
Impulse category: C1, C2, C3, D1
Max. continuous operating voltage: 30.0 V DC / 21.2 V AC
Nominal current: 0.5 A
C2 nominal discharge current (8/20 µs) per line: 10 kA
C2 Total nominal impulse discharge current (8/20 µs): 20 kA
D1 lightning impulse current (10/350 µs) per line: 1.5 kA
D1 total lightning impulse current (10/350 µs): 3 kA
Male thread 1/2-14 NPT, on one end
Enclosure in V4A, IP67
Max. continuous operating voltage DC (UC): 32 V
Max. continuous operating a.c. voltage (UC): 22.6 V
Nominal current (IN): 0.55 A
C2 Total nominal discharge current (8/20 µs) (In): 10 kA
C2 Nominal discharge current (8/20 µs) line-line (In): 150 A
D1 Lightning impulse current (10/350 µs) line-PG (Iimp): 1 kA
Cut-off frequency line-line (fG): 67 MHz
Degree of protection: IP 67
For mounting on (field / device side): 1/2-14 NPT male thread
Brand: DEHN
Type: DPI CD EXI+D EAS 15 N
Part No.: 929975
or equivalent.